In D2D mode, the TX IO communicates with LoRa Enless sensors (4 maximum) and controls its outputs according to the alarm thresholds configured on the sensors
Open the TX IO case by unscrewing the 4 cover screws.
Externally power your TX IO (between 7.5 and 24VDC). If you use our 12V power supply, connect your power supply to the POWER terminal of the receiver.
•Red wire connected to the V+ terminal block
•Black wire connected to the 0V terminal block
The procedure for accessing the TX IO configuration server is identical to that of the receiver. The default address for accessing the TX IO server is 192.168.77.77 (please avoid use on Microsoft Edge and favor use on Google Chrome).
Select the D2D operating mode from the CONFIG TX IO tab . Once selected, restart your TX IO so that the mode change is taken into account using the Reboot button from the TX IO server Admin tab
In the CONFIG D2D tab, you must declare the sensors you want to pair to the TX IO. The procedure is the same as when you declare sensors on a receiver
Configuring alarm thresholds is done from the advanced options
In the CONFIG TX IO tab, the relays can be associated with the alarm thresholds of the sensors that we have just configured.
To do this, for each relay select:
• The LoRa ID of the configured sensor
• The relay mode: normally closed or normally open
Normally closed : corresponds to a closed rest state. When the status is 0, the relay is closed. When the status is 1, the relay is open.
Normally open : corresponds to an open rest state. When the status is 0, the relay is open. When the status is 1, the relay is closed.
• The type of alarm to trigger a relay.
The activation of the sensors is done in the same way when pairing the sensors to the receiver.
In the STATUS tab , in the Transmitter Network section, the frames from the sensors that you have just activated must be sent at the periodicity that has been configured. This tab allows you to validate the correct reception of sensor frames. We recommend using this page as an on-site audit tool, to validate that RSSI levels for receiving probes are good.
Click Save to save your configuration.
In the STATUS tab in the Outputs section you can see the relay status display ON or OFF and the number of times the status has been switched from the TX IO power supply. You can test the relay status by clicking the Toggle Relay button. The relay activates for one second.
The TX IO relays are contact type, electronic mosfet relays without polarity. The maximum voltage between the two relay terminals is 48 VDC and the maximum current is 500 mA.
Rappel concernant les possibilités d'utilisation du TX IO 600-040
The TX IO offers Enless integrators different control possibilities. As a reminder, the TX IO has 2 contact-dry inputs and 4 controllable relay outputs. It can be used in 3 distinct modes which will be configurable from the server embedded in the transmitter.
By default, the TX IO is delivered ready to be used in remote control mode.
To change the mode of use of the TX IO, please access its configuration server (same procedure as for accessing the receiver server ).
Control of relay outputs on receiver commands
The configuration of the TX IO will be done from the receiver server with which the TX IO will communicate.
Below are the steps for configuring the TX IO.
Once declared on the receiver server and configured, you will need to activate the TX IO to pair it with the receiver. Below are the steps for activating the TX IO.
Validate that the TX IO communicates with the receiver.
The minimum delay between sending two commands to the TX IO is 2 seconds. If you send a second command before this 2 second delay, it will not be taken into account by the TX IO.
In the STATUS tab you can see the status display of the digital inputs and the counts since power-up. At the bottom of the tab you can see the relay status display ON or OFF and the number of times the status has been switched from the TX IO power supply.
You can test the relay status by clicking the Toggle Relay button. The relay activates for one second.
The TX IO relays are contact type, electronic mosfet relays without polarity. The maximum voltage between the two relay terminals is 48 VDC and the maximum current is 500 mA.
Control of relay outputs based on TX IO input status
Open the TX IO case by unscrewing the 4 cover screws.
Externally power your TX IO (between 7.5 and 24VDC). If you use our 12V power supply, connect your power supply to the POWER terminal of the receiver.
•Red wire connected to the V+ terminal block
•Black wire connected to the 0V terminal block
for accessing the TX IO configuration server is identical to that of the receiver. The default address for accessing the TX IO server is 192.168.77.77 (please avoid use on Microsoft Edge and favor use on Google Chrome).
Select the Local Control operating mode from the TX IO config tab . Once selected, restart your TX IO so that the mode change is taken into account using the Reboot button from the TX IO server Admin tab.
In the CONFIG TX IO tab , configure your relays by selecting for each relay:
• Input: input 1 or input 2
• The relay mode: normally closed or normally open
Normally closed : corresponds to a closed rest state. When the status is 0, the relay is closed. When the status is 1, the relay is open.
Normally open : corresponds to an open rest state. When the status is 0, the relay is open. When the status is 1, the relay is closed.
• The delay: 1 sec, 5 sec, 10 sec, 30 sec, 60 sec or 120 sec.
Click Save to save your configuration.
In the STATUS tab you can see the status display of the digital inputs and relays, as well as the number of status changes since power-up. You can test the status of the relays by clicking on the Toggle Relay button. The selected relay activates for one second. The TX IO is now configured, you can power it off.
In the CONFIG TX tab, refresh your browser page. A validation sticker should appear in front of the TX IO that you have just activated.
A red dot means that the configuration is being recovered. Do not hesitate to wait a few moments and refresh your page if the green dot does not appear.
In the NETWORK tab, the TX IO frames that you have just powered must be sent at the periodicity that has been configured. This tab allows you to validate the correct reception of the TX IO frames.
The TX IO relays are contact type, electronic mosfet relays without polarity. The maximum voltage between the two relay terminals is 48 VDC and the maximum current is 500 mA.
Once your TX IO is powered and connected to your PC, you can validate the correct behavior of the product using its LEDs.
To decode the status of the TX IO inputs from the receiver's Modbus table, please refer to .
for accessing the TX IO configuration server is identical to that of the receiver. The default address for accessing the TX IO server is 192.168.77.77 (please avoid use on Microsoft Edge and favor use on Google Chrome).
declaration of the TX IO is the same as for other transmitters.
To decode the status of the TX IO inputs from the receiver's Modbus table, please refer to .
Step 1
Power the TX IO (7.5 à 24VDC)
Step 2
Validate the TX IO LEDs behavior
Once your TX IO is powered and connected to your PC, you can validate the correct behavior of the product using its LEDs.
Open the TX IO case by unscrewing the 4 screws on the cover then supply your receiver externally (between 7.5 to 24VDC).
Remote control mode
The TX IO outputs are controlled by commands from the receiver. The TX IO also reports the status of its inputs to the receiver. In remote control mode, the TX IO behaves like any other Enless transmitter (sending periodic messages) while having the possibility of receiving commands from the receiver to control its 4 relay outputs
Local control mode
The TX IO controls its relay outputs according to the status of its inputs. It can send reporting messages to the receiver. The TX IO can be configured to synchronize inputs to relay outputs with a configurable delay (to ensure that the relay does not instantaneously match if there is a momentary change in the input state).
D2D (Device To Device) mode
The TX IO communicates with LoRa Enless sensors (4 maximum) and controls its outputs according to the alarm thresholds configured on the sensors