TX PULSE LED
Installing the optical read head on the meter
Last updated
Installing the optical read head on the meter
Last updated
The pulse optical reader records 1 pulse every 5 flashes.
Calculation formula = (A x 5) x B x C x D
A = Number of pulses measured
B = Pulse weight Blue tariff: 0.1W/pulse. In this case, enter 0.1 for B value in the calculation below. Other tariffs: Shown on the meterβs interface (label or screen)
C = TC ratio (Current transformation) Blue tariff: 1
Yellow tariff: 20, 40 or 100 (shown on the meterβs interface)
D = TT ratio (Tension transformer)
Blue tariff: 1
Yellow tariff: 1 Green tariff: Shown on the meterβs interface.
The calculation formula above is a calculation of consumption in Watt-hour (Wh). To get a value in Kilowatt-hour (kWh), you just need to divide the value by 1,000
Indicator light
Locate the flashing diode on the meter. It is on this diode that the optical reader will be positioned. The optical read head can only interpret LED flashes with a flashing duration of 3ms minimum and 100ms maximum.
Viewfinder attachment
Clean the meter around the flashing diode. Glue the viewfinder by aiming the diode through the hole (the viewfinder has adhesive)
Drive lock
Clip the reader into the viewfinder. Exert a uniform force over the entire surface of the sensor.
Checking
Once you power your transmitter, the red LED will light up periodically for 20 seconds, then the green LED will take over.