๐Ÿ“ŽTX PULSE LED

Installing the optical read head on the meter

Installing the optical read head

Cover

Viewfinder attachment

Locate the flashing diode on the meter and stick the viewfinder aiming the diode through the hole.

Cover

Locking the reader

Clip the reader into the viewfinder. Exert a uniform force over the entire surface of the sensor.

Cover

Fixation

Use the black screw to tighten the optical head to the viewfinder

Cover

Checking

Validate the correct positioning of the optical read head before powering the sensor

Consumption calculation

The pulse optical reader records 1 pulse every 5 flashes.

Calculation formula = (A x 5) x B x C x D

A = Number of pulses measured

B = Pulse weight Blue tariff: 0.1W/pulse. In this case, enter 0.1 for B value in the calculation below. Other tariffs: Shown on the meterโ€™s interface (label or screen)

C = TC ratio (Current transformation) Blue tariff: 1

Yellow tariff: 20, 40 or 100 (shown on the meterโ€™s interface)

D = TT ratio (Tension transformer)

Blue tariff: 1

Yellow tariff: 1 Green tariff: Shown on the meterโ€™s interface.

The calculation formula above is a calculation of consumption in Watt-hour (Wh). To get a value in Kilowatt-hour (kWh), you just need to divide the value by 1,000