Data reception
Validate that messages are correctly received from the NETWORK tab.
Last updated
Validate that messages are correctly received from the NETWORK tab.
Last updated
The sensor frames that you have just activated should go up in the NETWORK tab at the periodicity that has been configured. This tab allows you to validate the correct reception of sensor frames.
We recommend using this page as an on-site audit tool, to validate that the RSSI levels for receiving sensors are good.
Position the transmitters where they will be installed on site. We invite you to use the push button located on the electronic boards of the sensors to force the sending of test frames.
The LED L2 flashes when you press the push button. This means that a frame has been sent by the transmitter. You should see in the NETWORK tab that the test frame has been received correctly.
In case of weak RSSI, we recommend installing a signal repeater. To learn more about signal repeater installation, please visit this page .
Strong signal 🙂
Up to -105 dBm
Medium signal 😐
from -106 to -112 dBm
Weak Signal 🙁
beyond -112 dBm